Fire Alarm Cable Shielded 300V FAS

FT4 CSA UL

 

Solid bare copper conductors, PVC insulation, 100% aluminum foil shield, solid tinned copper drain, Red PVC jacket FT-4, -20° C to 105° C, 300 Volts, CSA and UL Approved.

Applications:

PCS
Catalogue
Number
Conductor Drain AWG Size Wall Thickness Nominal
O.D.
(inches)
Total
Weight
(lbs/km)
Colour Code Chart
No. AWG
Size
Stranding Insulation
(inches)
Jacket
(inches)
FA18-02CB1 2 18 Solid 22 .015 .030 .211 100 7
FA18-03CB1 3 18 Solid 22 .015 .030 .226 130 7
FA18-04CB1 4 18 Solid 22 .015 .030 .240 153 7
FA18-05CB1 5 18 Solid 22 .015 .030 .255 183 7
FA18-06CB1 6 18 Solid 22 .015 .032 .275 197 7
FA18-07CB1 7 18 Solid 22 .015 .032 .292 226 7
FA18-08CB1 8 18 Solid 22 .015 .032 .310 254 7
FA18-09CB1 9 18 Solid 22 .015 .032 .330 280 7
FA18-10CB1 10 18 Solid 22 .015 .032 .335 307 7
FA18-30CB1 30 18 Solid 22 .015 .040 .537 853 7
FA16-02CB1 2 16 Solid 22 .015 .030 .232 127 7
FA16-03CB1 3 16 Solid 22 .015 .030 .247 200 7
FA16-04CB1 4 16 Solid 22 .015 .030 .265 253 7
FA14-02CB1 2 14 Solid 22 .015 .030 .262 173 7
FA14-03CB1 3 14 Solid 22 .015 .032 .302 286 7
FA14-04CB1 4 14 Solid 22 .015 .032 .312 323 7
FA14-06CB1 6 14 Solid 22 .015 .032 .338 399 7
FA12-02CB1 2 12 Solid 22 .015 .032 .293 220 7

 

Aluminum or Steel Interlock Armour and Jacket available upon request.

¶ Grey Jacket available upon request

 

Applications:

  • FAS 105: Fire Alarm & Signal Cable for interconnection of electrical devices within a security and fire protective signaling system.  The cables are intended for installation according to Section 32 of the Canadian Electrical Code Part 1 2002 Edition.
  • LVT: Class 2 circuit wiring for installation according to Section 16 of the CEC Part 1 2002 Edition.
  • FT1: For installation in buildings of combustible construction (excluding plenum areas) per the CEC PT-1 1998 Edition Rule 2-126 and the National Building Code 1995 Edition Article 3.1.4.3.
  • FT4: For installation in buildings of non-combustible construction and plenum areas in any building per the CEC Part 1 Rule 2-126 and the National Building Code 1995 Edition Articles 3.1.5.17 and 3.6.4.3.

Notes

  • Unless otherwise permitted by local electrical inspection authorities, Section 32 (CEC Part 1) requires that non-metallic sheathed fire alarm cables used in non-combustible buildings be installed in conduit or metal armour (32-102), regardless of an FT4 designation.  As a cost-effective alternative to metal conduit, Fire Alarm Cable is available with an interlock aluminum armour.
  • B.C. and Ontario do not permit the use of FT4 cables in plenums unless enclosed in non-combustible raceway, i.e., metal conduit, or interlock armour.